%0 Journal Article %A Liang Chun %A Guangcai Gong %A Xi Fang %A Pei Peng %T Thermodynamic performance assessment of vacuum membrane-based dehumidification and air carrying energy radiant air-conditioning system (VMD-ACERS) %D 2021 %R 10.1016/j.cjche.2020.11.022 %J Chinese Journal of Chemical Engineering %P 217-227 %V 34 %N 6 %X Temperature and humidity independent control (THIC) air-conditioning system is a promising technology. In this work, a novel temperature and humidity independent control (THIC) system is proposed, namely VMD-ACERS, which integrates vacuum membrane-based dehumidification and air carrying energy radiant air-conditioning system. This work establishes a novel coefficient of performance (COP) model of VMD-ACERS. The main parameters affecting the COP of conventional fan coil unit cooling system (FCUCS) and VMD-ACERS are investigated. The performance of FCUCS and VMD-ACERS are compared, and the energy-saving potential of VMD-ACERS is proved. Results indicate that, for FCUCS, the importance ranking of parameters is basically stable. However, for VMD-ACERS, the importance ranking will be affected by FCU and refrigerant. The most important parameters of VMD-ACERS are condensation temperature and permeate side pressure. On the contrary, superheating, subcooling are relatively less important parameters. For VMD-ACERS, it is not necessary to pursue the membrane with very high selectivity, because the selectivity of membrane would also be a less important parameter when it reaches 500. The COP of VMD-ACERS is higher than that of FCUCS when the permeate side pressure is higher than 8 kPa. The VMD-ACERS solves two technical problems about power-saving and thermal comfort of conventional THIC, and can extend the application of THIC air-conditioning system. %U https://cjche.cip.com.cn/EN/10.1016/j.cjche.2020.11.022